Template 4: Dual Hazard - Split Release
B.4 Template 4: Dual Hazard - Split Release
OUTPUT CIRCUITS
#1 ALARM NAC
#2 SUPV BELL NAC
#3 RELEASE SOLENOID 1
#4 RELEASE SOLENOID 2
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).
Input Zone Types:
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay Timer 10 set to
secs.)
Zone 4 = Supervisory
Zone 5 = Manual Release
Zone 6 = Pull Station
Output Circuit Types:
Output 1 = Alarm NAC, silenceable, coded for steady on
Output 2 = Supervisory Bell NAC, silenceable, coded for steady on
Output 3 = Release Solenoid 1 (unsupervised for shorts)
Output 4 = Release Solenoid 2 (unsupervised for shorts)
Timers
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
Activation of Input Zone 1 (2-Wire Smoke) will operate Release Solenoid 1 Output #3 and
Alarm NAC Output #1. Activation of Input Zone 2 (Fire) will operate Release Solenoid 2 Out-
put #4 and Alarm NAC Output #1. Activation of Input 5 (Manual Release) or Input 6 (Manual
Pull Station) will operate Solenoid 1 Output #3 and Solenoid 2 (Output #4) and Alarm NAC
Output #1. Release Solenoid 1 will turn off water release following time-out of the 10 minute
Soak Timer 1 and Release Solenoid 2 will turn off water release following time-out of the 10
minute Soak Timer 2
Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a 10
second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 seconds
Activation of Input Zone 4 (Supervisory) will operate the Supervisory Bell NAC Output #2
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
Template 4: DUAL HAZARD - SPLIT RELEASE
1
2
2-WIRE SMOKE
FIRE
X
X
X
X
FACP Configuration Templates
INPUT ZONES
3
4
WATERFLOW
SUPV.
X
X
5
6
MANUAL
PULL
RELEASE
STATION
X
X
X
X
X
X