2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-
limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is
illustrated below.
*Note: In certain applications, an NAC (power-limited circuit) could be adjacent to a
releasing circuit (nonpower-limited without supervision kit REL-4.7K)
Power-limited Circuits
AC Power
120 VAC
Hot (L1)
Ground
Neutral (L2)
ground
stud
Figure 2.10 Typical UL Power-limited Wiring Requirements
28
Nonpower-limited Circuits*
(Class 2)
N-CAC-5X
Deluge - Preaction Control FACP
Power-limited Circuits (Class 2)
N-CAC-5X
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
Power-limited Wiring Requirements