Calculating The Battery Size; 1: Nfpa Battery Requirements; 2: Selecting And Locating Batteries - Honeywell Notifier RP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

Power Supply Calculations

5.4 Calculating the Battery Size

Use Table 5.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load
determines the battery size (in AH), required to support the control panel under the loss of AC
power. Complete Table 5.4 as follows:
1.
Enter the totals from Table 5.3 on page 89, Calculation Columns 2 and 3 where shown.
2.
Enter the NFPA Standby and Alarm times (refer to 'NFPA Requirements' below).
3.
Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere
hours.
4.
Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH).
5.
Write the ampere hour requirements on the Protected Premises label located inside the cabinet
door.
Secondary Standby Load
(total from Table 5.3 Calculation
Column 3)
[
Secondary Alarm Load
(total from Table 5.3 Calculation
Column 2)
[
Sum of Standby and Alarm Ampere Hours
Battery Size, Total Ampere Hours Required
Table 5.4 Total Secondary Power Requirements at 24 VDC
5.4.1 NFPA Battery Requirements
NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby power
followed by 5 minutes in alarm
5.4.2 Selecting and Locating Batteries
Select batteries that meet or exceed the total ampere hours calculated in Table 5.4. The control
panel can charge batteries in the 7 AH to 26 AH range. The control panel cabinet is capable of
housing batteries up to 18 AH. Batteries larger than 18 AH require the NFS-LBB, BB-26, or other
UL listed external battery cabinet.
For Canadian Applications, the minimum battery size is 12 AH and the maximum battery size is
18 AH.
90
Required Standby Time
(24 hours)
]
X[
Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)
]
X[
Multiply by the Derating Factor
]
=
]
=
=
X 1.2
=
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
Calculating the Battery Size
AH
AH
AH
AH

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier rp-2001eNotifier rp-2001c

Table of Contents