While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and indi-
cate the selection next to the Type option.
Output Circuit Map
INPUT ZONE #
1=OUTPUT CIRCUIT MAP
2=FREEZE SUPV.
Output Mapping (per input zone) allows the programmer/operator to assign the Output Circuits that
Edit Input Zone Screen #3
will be activated when a particular Input Zone or cross-zoned releasing group goes active. Pressing
1 for Output Circuit Map while viewing Edit Input Zone Screen #3 will display screens which show
the Output Circuits programmed to activate when the selected Input Zone (or cross-zoned releasing
group) is activated. Output Map Screen #1 displays the Output Type Codes and programming for
Output Circuits 1 through 3 and Output Map Screen #2 displays the Output Type Code and pro-
gramming for Output Circuit 4.
As an example, if Template 1 has been selected as the FACP Configuration [refer to"FACP
CONFIG (Application Templates)" on page 51], selecting the Output Circuit Map for Input Zone 1
will display the following screens:
The screens indicate that when Input Zone 1 is activated:
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
N/A
N/A
Waterflow
Waterflow NS (nonsilenceable)
Combo
Combo w/AutoResettable Superv
2-Wire Smoke
2-Wire Heat
N/A
Linear Heat
N/A
N/A
Fire
Low Pressure
Low Pressure AutoResettable2
High Pressure
High Pressure AutoResettable2
3
Disable Release
Supervisory
Supervisory AutoResettable2
N/A
2nd-Shot Water Switch
1 Activation of a Manual Release Switch will override Predischarge Delay, resulting
in an immediate water release.
2 AutoResettable means that a device with this type code, when activated, will
automatically reset when the corresponding condition is cleared.
3 Disable Release allows the installer to disable the releasing solenoids during
system testing. Disable Release will only work when the system is not in alarm.
4 The 2nd-Shot Water Switch provides the option of performing another immediate
water release manually. Refer to "2nd-Shot Water Switch" on page 81.
OUTPUT MAP ZONE 1
1=ALARM
NAC
2=WATERFLOW NAC
3=RELEASE 1
Output Map Screen#1
Output Circuit #1 default programmed as Alarm NAC will activate (Yes)
2
Fire/Supervisory, nonlatching
Supervisory, nonlatching
Supervisory, nonlatching
Supervisory, nonlatching (disables Release Circuits)
Supervisory, nonlatching
4
Fire Alarm, nonlatching
Table 3.1 Zone Types
OUTPUT MAP ZONE 1
4=SUPV BELL NAC N/A
YES
NO
YES
Output Zone Screen#2
Fire
Fire, nonsilenceable
Fire/Supervisory
Fire Alarm
Fire Alarm
Fire Alarm
Fire Alarm
Supervisory, latching
Supervisory
Supervisory, latching
Programming
53