Honeywell Notifier RP-2001 Instruction Manual page 104

Pre-action/deluge control panel
Table of Contents

Advertisement

FACP Configuration Templates
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3 (Water-
flow - with Waterflow Delay time) or Zone 5 (Manual Release) or Zone 6 (Pull Station) will
operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 4 (Supervisory) will operate the Supervisory Relay
Device Installation Example for Template 4
Output Circuit #1
Alarm NAC
Output Circuit #2
Supv Bell NAC
Notes:
1.
Waterflow Delay is programmed for 10 seconds.
2.
All End-of-Line Resistors, illustrated in this example, are 4.7KΩ, ˝ watt (PN: 71252).
3.
All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to "N-CAC-5X Class A Converter Module" on page 29.
104
Input Circuit #1
2-Wire Smoke
Input Circuit #2
Fire (Heats)
Input Circuit #3
Waterflow
1
Input Circuit #4
Supervisory
Input Circuit #5
Manual Release
Template 4: Dual Hazard - Split Release
Input Circuit #6
Pull Station
Output
Output
Circuit #3
Circuit #4
Release
Release
Solenoid 1
Solenoid 2
RP-2001 Series Manual — P/N 52985:D5 1/26/2017