Advertisement

Plug the FDT UPIC cable into port T10 of the upper BPC.
7. Login to the HMC with the User ID hscroot.
Use the HMC that is connected to the BPA where the FDT is plugged.
8. From the HMC left Navigation menu, expand Systems Management then select Frames.
Verify frame serial number for the frame to be serviced.
9. In the Frames view on the HMC, place a checkmark in the Select column for the frame to be
serviced.
10. Verify that the frame Status is Rack Standby/Rack Standby or Standby/Standby.
• If frame Status reads Rack Standby/Rack Standby or Standby/Standby – OK.
Continue to next step.
• If frame Status does not read Rack Standby/Rack Standby or Standby/Standby –
action required. Contact next level of support.
11. From the Task menu on the HMC, select Serviceability > Hardware > Fill and Drain Tool
Tasks > Fill and Drain Command Interface
Fill and Drain Tool Command Interface will display. See below for a sample image of the
interface (FDT deactivated).
Power775 Disk Enclosure Chassis Service Procedure
---- Appendix D: DE Drain Procedure ----
Page 112 of 171