IBM Power775 Service Procedure page 104

Disk enclosure chassis service procedure
Hide thumbs Also See for Power775:
Table of Contents

Advertisement

• Error Status:
27. If the sight glass in HA2 never becomes full of water:
Ensure all hose connections in Step 18 through Step 23 are made properly.
Complete the diagnostics in Step 26.
• If the sight glass in HA2 becomes full of water, continue with procedure.
• If the sight glass in HA2 does not become full of water, contact next level of
support.
28. When the sight glass in HA2 has been mostly solid water for 60 seconds:
Click the Reset FDT button.
29. Click the Get FDT Status button and review the following:
• Tool mode:
• Error Status:
30. The DE fill procedure has completed successfully.
The DE can be connected to the system manifolds.
31. Disconnect the HA1 hose assembly from the left side DE water connection.
Power775 Disk Enclosure Chassis Service Procedure
---- Appendix C: DE Fill Procedure ----
Once FDT tank level is Full or Upper Half return to Step 18
and continue with procedure.
NONE – OK. Proceed to next step.
WARNING – click the Decode Error Status button, record
information returned and proceed to next step.
CRITICAL – click the Decode Error Status button, record
information returned and contact next level of support.
Ready – OK. Check Error Status.
System/Component Fill Mode – water pump still running.
Repeat Step 28.
NONE – OK. Proceed to next step.
WARNING – click the Decode Error Status button, record
information returned and proceed to next step.
CRITICAL – click the Decode Error Status button, record
information returned and contact next level of support.
Page 104 of 171