IBM Power775 Service Procedure page 100

Disk enclosure chassis service procedure
Hide thumbs Also See for Power775:
Table of Contents

Advertisement

• Component Pressure Test: Pass – OK. Proceed to next step.
16. Verify DE main water connections are not connected to system manifolds.
17. Before proceeding, read required safety information:
CAUTION:
The water-based coolant solution may contain an additive intended to inhibit
corrosion (or provide other functions). The solution may cause irritation to the skin or
eyes. Avoid direct contact with the solution. Employ appropriate Personal Protective
Equipment when performing operations involving the coolant or which may potentially
expose you to the coolant. Refer to the MSDS for more information. (C037)
CAUTION:
Protective eyewear is needed for the procedure. (L011)
CAUTION:
Chemical resistant gloves are needed for this procedure. (L014)
DANGER:
Risk of electric shock due to water or a water solution which is present in this
product. Avoid working on or near energized equipment with wet hands or when spilled
water is present. (L016)
18. Remove hose assembly HA1 from the upper tool storage compartment.
Connect either end of hose assembly HA1 to the TS connection on the front panel of
the FDT.
Power775 Disk Enclosure Chassis Service Procedure
---- Appendix C: DE Fill Procedure ----
Exit this procedure and perform a Fill and Drain Tool (FDT)
Tank Fill Procedure.
Once FDT tank level is Full or Upper Half, return to this step
and continue with procedure.
This procedure should not be continued if the
component pressure test did not Pass.
Incomplete or Fail – action required.
Exit this procedure and complete a DE
Pressure Test Procedure.
Once a passing result is confirmed, return to
this step and continue with procedure.