Chapter 3: Configuration
As long as IncSignal is active the output increases at a rate set by the parameter
Time. As long as DecSignal is active the output decreases at a rate set by the
parameter Time.
When TrackEnable is false, the value of the Value output is controlled by the
IncSignal and the DecSignal inputs. When activating DecSignal, Value will not
decrease below LoLimit, and when activating IncSignal, Value will not increase
above HiLimit.
When TrackEnable is true, the value of the TrackSignal input is copied to the
Value output. The IncSignal and DecSignal inputs are disregarded when
TrackEnable is true.
The function of LoLimit and HiLimit always applies.
Note: If the inputs (IncSignal and DecSignal) are equal (both False or both True)
the value of the output does not change.
493-0736-11 (6-2)
LoLimit ≤ Value ≤ HiLimit