Chapter 3: Configuration
Value
Table 9
To enable an Analog User Block, set the parameter Mode to on. To disable the
block set Mode to Off.
To set the number of decimals displayed for the signal value configure the
parameter NumberOfDecimals. This also defines the step increase/decrease, i.e.
NumberOfDecimals =1, step = 0.1, NumberOfDecimals = 2, step = 0.01.
Each user defined input must lie within a specified range. Configure the
parameters LoLimit and HiLimit to set this range.
The output of this type of block is always in the range –100.0% to +100.0%.
Lolimit always represents the value –1.0 (–100%) and HiLimit the value 1.0
(100%).
Each block may be given a twenty letter identification name by configuring the
parameter Identity.
There are two ranges to keep track of:
• Signal Range
• Displayed Range
493-0736-11 (6-2)
Name
Analog User Block Outputs.