Chapter 3: Configuration
NumberOf
Decimals
MinValue
MaxValue
Unit
Tag
Table 141
Example
A sensor provides a 4–20 mA output for a calibrated flow range of
0 to 9 m
present the Process Value and Set Point with two decimals?
4 mA represents a flow of 0 m
Set NumberOfDecimals to 2, then set MinValue to 0.00 and MaxValue to 9.00.
493-0736-11 (6-2)
Name
0 ≤ NumberOfDecimals ≤ 4
–99999 ≤ MinValue ≤ MaxValue ≤ 99999
–99999 ≤ MinValue ≤ MaxValue ≤ 99999
%, °C, °F, K, W, kW, MW, J, kJ, MJ, rpm, Pa,
kPa, MPa, bar, mbar, bara, l, l/s, l/min, l/h, Psi,
Psig, Psia, mmWG, "WG, mmvp, mvp, mmH
mmHg, "Hg, kp/cm
3
Nm
/h, m
ppm, pH, mg/l, feet, inches, meters, tons, lbs,
lbs/sec, lbs/min, lbs/hr, ft/sec, ft/hr, BTU/hr,
3
BTU, ft
MPPH, cc, cm, GPM.
User defined text.
Process Value Parameters.
3
/min. How should MinValue and MaxValue be set if the user wants to
Parameters
Setting
2
2
, N/m
, kg/cm
3
/h, t/24h, m/s, m/min, µs, µs/cm,
3
/sec, ft
/hr, gals, gal/sec, gal/hr, cu.ft,
3
/min, and 20 mA represents a flow of 9 m
3.6 Setting the Configuration
Unit
None
None
None
None
O,
2
2
, kg/h, t/h,
None
3
/min.
185