Chapter 3: Configuration
Disabling Alarms
You may selectively disable the deviation alarms as follows:
NegAlarm: Set NegDeviationLimit to –100.0.
PosAlarm: Set PosDeviationLimit to 100.0.
Signal1
Signal2
Table 93
Mode
NegDeviationLimit
PosDeviationLimit
Identity
Table 94
493-0736-11 (6-2)
PosAlarm = Diff > PosDeviationLimit
NegAlarm = Diff < NegDeviationLimit
Alarm = PosAlarm OR NegAlarm.
Name
Deviation Alarm Inputs.
Name
Off, On
–100.0 ≤ NegDeviationLimit ≤ 0.0
0.0 ≤ PosDeviationLimit ≤ 100.0
User defined text
Deviation Alarm Parameters.
Inputs
Connection
Analog
Analog
Parameters
Setting
3.6 Setting the Configuration
Unit
None
%
%
None
135