3.6 Setting the Configuration
• The Tuning process can be interrupted by pressing the Hand key. In this case
Figure 52
After an autotuning sequence the Control Mode is always Auto.
Tuning Conditions
The Tuning conditions are summarised below.
Manual Control Mode (and Set Point RampMode ≠ Off)
Auto Control Mode (and set Point RampDone = True)
Using Feed Forward with Mode = Static Gain
Using Three State Pulse output without feedback
Forced Output Control Mode
Tracking Control Mode
Set Point Ramp not done
Table 109
150
no changes are made to the controller's parameters.
Display – Tuning Process.
Tuning Conditions.
To Tune Press
Tune
Temp Tank 4
21.7 °C
I Tuning Init
Temp Tank 4
21.7 °C
I Tuning Phase 1
State
Chapter 3: Configuration
ISP
ISP
Tuning Possible
Yes
Yes
No
No
No
No
No