3.6 Setting the Configuration
Computer Mode
ErrOr Warn
Table 148
COM Setup
There are five parameters associated with communications:
• ComProtocol which may be set to COMLI or MODBUS RTU.
• Identity which may be set to any number within the range 1 to 247
• RS-485BaudRate which may be set to a maximum value of 38,400 baud.
• RS-232BaudRate which may be set to a maximum value of 38,400 baud
• WriteEnable which may be set to On or Off.
Communication modes can be switched both from the front and via the
ComputerModeEnable input (described above). The Front Switch (via the
Operator Option List) and ComputerModeEnable have equal priorities.
If WriteEnable is set to Off, a supervisory system can not write to the controller´s
registers when the Communication Mode is Local.
Local
Computer
Table 149
Note. See Appendix E for a full list of communication I/O bits and registers
194
Name
System Status Outputs.
Communication
Mode
Impossible
Possible
WriteEnable is Off.
Outputs
False = Local, True = Computer
Refer to Appendix B for more information
Write Operations
Chapter 3: Configuration
Type
Operator Front Panel
Access
Unrestricted
Restricted
493-0736-11 (6-2)