Outline of Control (Indoor Unit)
6.3

Thermostat Control with Operation Mode Set to AUTO

The system will conduct this temperature control shown below, only when the wireless remote
controller or any central remote controller is connected.
Furthermore, setting changes of the differential value (D) can be made.
Mode
First code
No.
No.
12
Differential value while in AUTO
4
(22)
Heating thermostat OFF
Heating thermostat ON
128
Contents of setting
operation mode
Set heating temperature
(A – D)
Display change
Cooling o Heating
3qC (5.4qF)
(Ex.) When automatic cooling temperature is set to 27qC (80.6qF):
Differential value: 0qC (0qF)
Set cooling/ heating temp.
30qC
25qC
27qC
(86qF)
(77qF)
(80.6qF)
Cooling mode
Control temp.
Heating mode
Differential value set to 1qC (1.8qF)
Set heating temp. Set cooling temp.
26qC
27qC
29qC
(78.8qF)
(80.6qF)
(84.2qF)
24.5qC
(76.1qF)
Control temp.
Heating mode
Differential value set to 2qC (3.6qF)
Set heating temp. Set cooling temp.
25qC
27qC
28qC
(77qF)
(80.6qF)
(82.4qF)
24qC
(75.2qF)
Control temp.
Heating mode
Differential value set to 3qC (5.4qF)
Set heating temp. Set cooling temp.
24qC
27qC
(75.2qF)
(80.6qF)
23.5qC
(74.3qF)
Control temp.
Heating mode
Second code No.
01
02
03
0°C
1°C
2°C
0°F
1.8°F
3.6°F
Set cooling temperature
A
D
Display change
Heating o Cooling
D
(
+ 2)qC
2
D
(
+ 3.6)qF
2
Differential value set to 4qC (7.2qF)
Set heating temp.
23qC
(73.4qF)
Heating mode
Differential value set to 5qC (9qF)
Set heating temp.
22qC
22.5qC
Cooling
(71.6qF)
(72.5qF)
mode
Heating mode
Differential value set to 6qC (10.8qF)
Set heating
temp.
22qC
Cooling
(71.6qF)
(75.2qF)
mode
21qC
(69.8qF)
Heating mode
Differential value set to 7qC (12.6qF)
Set heating
temp.
21.5qC
(70.7qF)
(73.4qF)
Cooling mode
20qC
(68qF)
Heating mode
04
05
06
3°C
4°C
5°C
5.4°F
7.2°F
9.0°F
10.8°F
Cooling thermostat ON
Cooling thermostat OFF
Set cooling temp.
26qC
27qC
(78.8qF)
(80.6qF)
Cooling mode
Control temp.
Set cooling temp.
25qC
27qC
(77qF)
(80.6qF)
Cooling mode
Control temp.
Set cooling temp.
24qC
27qC
(80.6qF)
Cooling mode
Control temp.
Set cooling temp.
23qC
27qC
(80.6qF)
Cooling mode
Control temp.
Part 4 Functions and Control
SiUS281811EA
: Factory setting
07
08
6°C
7°C
12.6°F