Swing Flap Motor Abnormality - Daikin SkyAir RZR-TA Series Service Manual

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

Troubleshooting by Error Codes

4.13 Swing Flap Motor Abnormality

A7
Error Code
Applicable
FHQ-P, FHQ-M
Models
Method of Error
Utilizes ON/OFF of the limit switch when the motor turns.
Detection
Error Decision
When ON/OFF of the micro-switch for positioning cannot be reversed even though the swing flap
Conditions
motor is energized for a specified amount of time (about 30 seconds).
∗ Error code is displayed but the system operates continuously.
Supposed
 Defective swing motor
Causes
 Defective connection cable (power supply and limit switch)
 Defective micro-switch
 Defective indoor unit main PCB
230