Daikin SkyAir RZR-TA Series Service Manual page 171

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA
1.5.29 Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor unit fan carries
out residual operation for 1 minute after the thermostat is stopped. (For the purpose of preventing
dust on the air filter from falling off.)
1.5.30 Drain Pump and Humidifier Interlock Selection
This is used to interlock the humidifier with the drain pump. When water is drained out of the unit,
this setting is unnecessary.
Mode
15 (25)
1.5.31 Individual Ventilation Setting
This is set to perform individual operation of energy recovery ventilator using the remote
controller/central unit when heat reclaim ventilation is built in.
(Switch only when heat reclaim ventilation is built in.)
Mode
15 (25)
1.5.32 Display of Error Codes on the Remote Controller
For BRC1E series only
Error code (four digits) is displayed for limited products.
Select two-digit display if four-digit display is not preferred.
Mode
Part 5 Field Settings and Test Operation
Mode No.
First Code No.
15 (25)
2
First Code
Second Code
No.
No.
No.
01
3
02
First Code
Second Code
No.
No.
No.
01
5
02
First Code
Second Code
No.
No.
No.
01
02
1b
4
03
04
Field Setting from Remote Controller
Second Code No.
01
02
Contents
Not interlocked
Interlocked
Contents
— (Normal) 
Individual
Contents
Two-digit display
Four-digit display
: Factory setting
Contents
Not equipped
Equipped
: Factory setting
: Factory setting
: Factory setting
165