Check

5.14 Electronic Expansion Valve Coil Check

CHECK 18
Measure the connector pin-to-pin resistance and make sure that the resistance value is within the
range listed in the table below.
FCQ-TA, FTQ-TA
FBQ-P, FAQ-TA
308
Orange 1
Yellow 3
Measuring points
1 - 6
2 - 6
3 - 6
4 - 6
White 1
Yellow 2
Orange 3
Blue 4
Red 5
Brown 6
Measuring points
1 - 3
1 - 5
2 - 4
2 - 6
Red 2
Black 4
— 5
Gray 6
Judgment criteria
35-55 Ω
Judgment criteria
300 Ω
150 Ω
300 Ω
150 Ω
SiUS281811EA