Field Setting from Remote Controller
1.5.13 Optional Accessories Output Selection
Using this setting, "operation output signal" and "abnormal output signal" can be provided. Output
signal is output between terminals X1 and X2 of "adaptor for wiring", an optional accessory.
Mode
12 (22)
1.5.14 External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The input
is performed from the T1-T2 terminal of the operation terminal block in the electrical component
box.
Mode
12 (22)
1.5.15 Thermostat Differential Changeover
Differential value during thermostat ON/OFF control can be changed.
Factory Setting
FCQ-TA, FHQ-P, FHQ-M, FTQ-TA
FAQ-TA, FBQ-P
160
First Code
Second Code
No.
No.
No.
01
02
03
04
0
05
06
07
First Code
Second
No.
No.
Code No.
01
02
1
03
04
05
Mode No.
First Code No.
12 (22)
2
Model
Contents
Indoor unit thermostat ON/OFF signal is provided.
Output linked with ON/OFF of remote controller is provided.
In case of Error Display appears on the remote controller, output is
provided.
Only for FBQ-P
Economizer (field supply) ON/OFF signal is provided.
F2 T1 T2
Forced OFF
Input A
Contents
ON: Forced OFF (prohibition of using the remote controller)
OFF: Permission of using the remote controller
OFF → ON: Operation
ON → OFF: Stop
ON: Operation
OFF: The system stops, then the applicable unit indicates A0. The
other indoor units indicate U9.
Only for FBQ-P
ON: Economizer (field supply) is connected.
OFF: Not connected
Second Code No.
01
02
Second Code No.
01
02
SiUS281811EA
: Factory setting
: Factory setting
Contents
1.0ºC (1.8ºF)
0.5ºC (0.9ºF)
Contents
1.0ºC (1.8ºF)
0.5ºC (0.9ºF)
Part 5 Field Settings and Test Operation