Daikin SkyAir RZR-TA Series Service Manual page 245

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA
Note(s)
∗1. Pull out and insert the connector once and check it is absolutely connected.
∗2. Method to check transmission part of indoor unit main PCB.
Determination
∗ After confirmation, turn OFF the power, take off the short circuit and connect X70A
back to original condition.
Part 6 Service Diagnosis
(1) Turn OFF the power and remove the connector X70A of indoor unit main PCB
(A1P).
(2) Short circuit X70A.
(3) After turning ON the power, check below numbers under field setting from
remote controller.
(Confirmation: Second code No. at the condition of first code No. 21 on mode No.
41)
01: Normal
Other than 01: Transmission error on indoor unit main PCB
Troubleshooting by Error Codes
239