Daikin SkyAir RZR-TA Series Service Manual page 254

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

Troubleshooting by Error Codes
Troubleshooting
248
Diagnosis procedure 2
Infrared floor sensor error
(Error code CE-02)
Is the
connection
of the connector
on infrared floor
sensor PCB (A3P) and
the connector
X2A on A2P
normal?
YES
Is the
connection of the
sensor connector
normal?
YES
Check infrared floor sensor output; refer to sensor
and address data No. 26.
Displays
"--" by the above
verification method.
YES
Turn off the power and then reconnect.
Displays CE-02
again or "--" for
sensor and
address data.
YES
NO
Connect the connector correctly.
NO
Connect the connector correctly.
NO
Normal.
NO
Normal.
Replace the sensor.
SiUS281811EA
Part 6 Service Diagnosis