Daikin SkyAir RZR-TA Series Service Manual page 67

Cooling only 60 hz, heat pump 60 hz
Hide thumbs Also See for SkyAir RZR-TA Series:
Table of Contents

Advertisement

SiUS281811EA
Model
Indoor unit
name
Outdoor unit
Power supply
1 4 Cooling capacity
2 4 Heating capacity
3 4 Heating capacity
SEER (Rated)
EER (Rated)
HSPF (Rated)
Indoor unit
Casing color
Dimensions: (H×W×D)
Coil
Type
Rows×Stages×FPI
Face area
Fan
Model
Type
Motor output
Airflow rate (HH/H/L)
External static
pressure
Sound pressure level (HH/H/L)
Air filter
Weight
Connecting
Liquid Pipe
Pipes
Gas Pipe
Drain Pipe
Remote controller
Wired
(option)
Wireless
Outdoor unit
Casing color
Dimensions: (H×W×D)
Coil
Type
Rows×Stages×FPI
Face area
Compressor
Model
Type
Motor output
Fan
Model
Type
Motor output
Airflow rate
Weight
Sound pressure level
Connecting
Liquid Pipe
Pipes
Gas Pipe
Drain Pipe
Safety devices
Capacity Control
Refrigerant control
Ref.
Standard length
piping
Max. length
Max. height
difference
Refrigerant
Model
Charge
Ref. oil
Model
Charge
Drawing
Specification
No
Sound (indoor)
Sound (outdoor)
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m).
3 Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 17°FDB (−8.3°CDB), 15°FWB (−9.4°CWB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m).
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable in 14 stages within the < > range by remote controller.
6 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.
Part 1 General Information
FBQ42PVJU
RZQ42TAVJUA
1 phase, 208/230 V, 60 Hz
Btu/h
40,500 (11.9)
(kW)
Btu/h
47,000 (13.8)
(kW)
Btu/h
25,000 (7.3)
(kW)
Btu/h∙W
FBQ42PVJU
Galvanized steel plate
in (mm)
11–13/16 × 55–1/8 × 27–9/16 (300 × 1,400 × 700)
Cross fin coil
3 × 16 × 15
2
ft² (m
)
4.12 (0.383)
Sirocco fan
W
cfm
1,400/1,165/988 (39.6/33.0/28.0)
3
(m
/min)
inH
O
2
Standard 0.40 <0.80-0.20> (100 <200-50>) 5
(Pa)
dB(A)
44.0/42.0/40.0
lbs (kg)
in (mm)
φ3/8 (φ9.5) (Flare connection)
φ5/8 (φ15.9) (Flare connection)
in (mm)
in (mm)
VP25 (External dia. 1–1/4 (32), internal dia. 1 (26))
BRC1E73, BRC2A71
BRC4C82, BRC082A43
RZQ42TAVJUA
Ivory white
in (mm)
52–15/16 × 35–7/16 × 12–5/8 (1,345 × 900 × 320)
Cross fin coil
2 × 60 × 19
2
ft² (m
)
12.2 (1.134)
2YC90FXD#A
Hermetically sealed swing type
kW
Propeller fan
W
cfm
3,741 (106)
3
(m
/min)
lbs (kg)
225 (102)
dB(A)
in (mm)
φ3/8 (φ9.5) (Flare connection)
in (mm)
φ5/8 (φ15.9) (Flare connection)
φ1 (φ26) (Hole)
in (mm)
High pressure switch, Outdoor fan driver overload
protector, Inverter overload protector, Fusible plugs, Fuse
%
Electronic expansion valve
ft (m)
ft (m)
ft (m)
lbs (kg)
DAPHNE FVC50K
L
C: 4D126352
C: 4D075282A
C: 4D101949D
16.0
10.1
8.8
350
—6
102 (46)
3.5
P47N
70 × 2
57
protector, Inverter overload protector, Fusible plugs, Fuse
14-100
25 (7.6)
230 (70)
98 (30)
R-410A
7.9 (3.6)
1.52
FBQ48PVJU
RZQ48TAVJUA
1 phase, 208/230 V, 60 Hz
48,000 (14.1)
54,000 (15.8)
28,000 (8.2)
14.0
8.6
8.4
FBQ48PVJU
Galvanized steel plate
11–13/16 × 55–1/8 × 27–9/16 (300 × 1,400 × 700)
Cross fin coil
3 × 16 × 15
4.12 (0.383)
Sirocco fan
350
1,400/1,165/988 (39.6/33.0/28.0)
Standard 0.40 <0.80-0.20> (100 <200-50>) 5
44.0/42.0/40.0
—6
102 (46)
φ3/8 (φ9.5) (Flare connection)
φ5/8 (φ15.9) (Flare connection)
VP25 (External dia. 1–1/4 (32), internal dia. 1 (26))
BRC1E73, BRC2A71
BRC4C82, BRC082A43
RZQ48TAVJUA
Ivory white
52–15/16 × 35–7/16 × 12–5/8 (1,345 × 900 × 320)
Cross fin coil
2 × 60 × 19
12.2 (1.134)
2YC90FXD#A
Hermetically sealed swing type
3.5
P47N
Propeller fan
70 × 2
3,741 (106)
225 (102)
57
φ3/8 (φ9.5) (Flare connection)
φ5/8 (φ15.9) (Flare connection)
φ1 (φ26) (Hole)
High pressure switch, Outdoor fan driver overload
14-100
Electronic expansion valve
25 (7.6)
230 (70)
98 (30)
R-410A
7.9 (3.6)
DAPHNE FVC50K
1.52
C: 4D126352
C: 4D075282A
C: 4D101949D
Specifications
61

Hide quick links:

Advertisement

Table of Contents
loading