Setting Mode 1

This mode is used to set and check the following items.
1. Set items
2. Check items
Part 5 Field Settings and Test Operation
In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
COOL/HEAT selection (IND)
COOL/HEAT selection (MASTER)
COOL/HEAT selection (SLAVE)
The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Field Settings from Outdoor Unit
Used to select COOL or HEAT by individual
outdoor unit (factory setting).
Used to select COOL or HEAT by outdoor unit
group with the master unit.
Used to select COOL or HEAT by outdoor unit
group with the slave unit.