Part 4 Functions and Control
• No fan motor system error
• High pressure condition: ON (∗1)
• Liquid pipe temperature condition: ON (∗2)
• Heater ON permission (Defrost/oil Return): 0 (∗4)
&
&
• Not during defrost/oil return
OR
• Heater ON permission (Defrost/oil return): 1 (∗4)
• No fan motor system error
• During defrost/oil return
&
• Heater ON permission (Defrost/oil return): 1 (∗4)
• Not during defrost/oil return
• Fan motor system error
OR
• Heater ON permission (Defrost/oil return): 0 (∗4)
High pressure condition
Liquid pipe temperature condition
Auxiliary heater enabled
• Electric heater setting (Field setting 11 (21)-3): 2, 4, 6, 8, 10, 12 (∗6)
1:
&
• Electric heater capacity setting ≠ 01
0: Other than the above
Heater ON permission (Defrost/oil return)
1: Electric heater setting (Field setting 11 (21)-3): 8, 10, 12 (∗6)
0: Electric heater setting (Field setting 11 (21)-3): 2, 4, 6 (∗6)
Field setting 11 (21)-5. Refer to page 157.
Refer to page 157.
ON
OFF
49
54
120.2
129.2
ON
OFF
46
49
114.8
120.2
Outline of Control (Indoor Unit)
Tc
(˚C)
(˚F)
TH2
(˚C)
(˚F)