SiUS281811EA
4.32 Outdoor Fan Motor Abnormality
E7
Error Code
Applicable
All outdoor units
Models
Method of Error
The fan motor circuit error is detected based on the rotation frequency detected by Hall IC during
Detection
the fan motor operation.
Error Decision
In the condition of fan motor rotation, the number of rotation is below the fixed number for more
Conditions
than 6 seconds. (System down is caused by 4 times of detection.)
Supposed
Defective fan motor
Causes
Defect or connection error of the connectors/ harness between the fan motor and PCB
The fan can not rotate due to obstruction of foreign matter.
Clear condition: Continue normal operation for 5 minutes
Missing phase L1 and missing phase N
Part 6 Service Diagnosis
Troubleshooting by Error Codes
259