Point Name/Description
Airside Linkage Status – If Active, the controller is part of a linked system. If Not Active,
the controller is a stand-alone device.
If Airside Linkage Status is Active, the following information is received from the Zoning
System Master Zone, as applicable:
Occupancy Status
Space Temperature
Occupied Cooling Setpoint
Occupied Heating Setpoint
Unoccupied Cooling Setpoint
Unoccupied Heating Setpoint
Indoor Air CO2
Space Relative Humidity
Linkage Optimal Start
The following information is sent back to the Zoning System Master Zone:
Air Source Mode
Air Source Supply Air Temp
Air Source Outdoor Air Temp

I/O Points

The values shown on the I/O Points Properties page are the raw values at the I/O objects and may not match values
shown on status displays that are affected by control program logic.
i-Vu® users logged in as Power User and above are able to edit various parameters associated with the input channels and
the display names for all channels.
We strongly recommend that you leave these parameters at their defaults. The RTU Open is not a programmable controller.
I/O can only be used for the purpose designed in the equipment control program. Modifying these parameters may result
in unpredictable equipment control.
See Wiring inputs and outputs (page 13) for more information. This table lists each of the I/O Channels, their functions,
associated hardware, and terminal numbers.
Navigation:
i-Vu® / Field Assistant:
Point Name/Description
SPT Sensor/Zone Temp
SPT Sensor - (For the SPT Standard, SPT Plus, and SPT Pro sensors only). Sensor configurations on the microblock's
Properties > Details tab are listed below. For more information, see the Carrier Sensors Installation Guide.
input 1 – Input Channel 1; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space Relative Humidity.
input 2 – Input Channel 2; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space Relative Humidity.
input 6 – Input Channel 6; 10K Thermistor only. Supply Air Temperature.
RTU Open v3
Installation and Start-up Guide
Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
Properties
I/O Points
>
89
Range
R:
Active/Not Active
CARRIER CORPORATION ©2019
All rights reserved