Sequence Of Operation; Occupancy - Carrier RTU Open v3 Installation And Startup Manual

Hide thumbs Also See for RTU Open v3:
Table of Contents

Advertisement

Sequence of Operation

Sequence of Operation
The RTU Open supports various types of constant volume air source configurations:
Standard heat/cool unit types with up to 2-stages of mechanical cooling and gas or electric heating
Heat pump units utilizing a reversing valve output for heating and cooling control
Heat pump unit (Carrier) with an OEM defrost control board
Economizer, CO2, Demand Limiting, and RH control strategies are available for appropriately equipped units
LC WeatherExpert™ unit with 3-stage compressor control and variable speed supply fan control.
The RTU Open may operate as part of a VVT system using Airside Linkage or as a stand-alone controller.

Occupancy

The RTU Open's operation depends upon its occupancy state (Occupied/Unoccupied). The RTU Open operates
continuously in the Occupied mode until you configure an occupancy schedule.
An occupancy schedule may be:
A local schedule configured in the controller using an Equipment Touch or Field Assistant
A BACnet schedule configured in the i-Vu® application, networked through an i-Vu® Open Router
A BACnet or local schedule configured for subordinate VVT Zones, networked through an i-Vu® Open
Router(s) and employing Linkage
To set up occupancy schedules, see the documentation for your user interface.
NOTE A BACnet schedule, downloaded from the i-Vu® application will overwrite a local schedule that was set up
with an Equipment Touch or Field Assistant.
Occupancy Source - the following settings determine occupancy.
Options:
Always Occupied – (default) Controller operates continuously, regardless of any configured schedule
BACnet Schedule – Uses a local BACnet occupancy schedule configured within the controller
BAS On/Off – Occupancy is set over the network by another device or a third party BAS. Refer to the RTU
Open Integration Guide for additional instructions in communication protocols.
Remote Occ Input – Controller monitors an input contact connected to one of the available binary inputs
configured to receive it. You must set Unit Configuration > Occupancy Source to Remote Occ Input and one
Input Switch Configuration to Remote Occupancy.
RTU Open v3
Installation and Start-up Guide
44
CARRIER CORPORATION ©2019