Appendix C: RTU Open Points/Properties on the Equipment Touch
Performance - Equipment Touch
Navigation:
Equipment Touch:
Point Name/Description
Current Performance Data
Equipment Runtime – RTU Open's hours of operation since the last reset of
Performance Data.
Economizer Utilization – Percentage of Equipment Runtime hours that are above the
active Economizer time since the last reset of Performance Data.
DCV Utilization – Percentage of Equipment Runtime hours that are above the active
DCV time since the last reset of Performance Data.
Unocc Free Cool Utilization – Percentage of Equipment Runtime hours that are above
active Unoccupied Free Cooling since the last reset of Performance Data.
Part Load Cooling Utilization – Percentage of Equipment Runtime hours that are above
Cooling time in which less than the maximum configured cooling stages were active
since the last reset of Performance Data.
Full Load Cooling Utilization – Percentage of Equipment Runtime hours that are above
Cooling time in which all of the configured cooling stages were active since the last
reset of Performance Data.
Heating Utilization – Percentage of Equipment Runtime hours that are above active
Heating time since the last reset of Performance Data.
Recorded High OAT – Maximum recorded OAT since the last reset of Performance
Data.
Recorded Low OAT – Minimum recorded OAT since the last reset of Performance Data.
Alarms - Equipment Touch
Navigation:
Equipment Touch:
Point Name/Description
Click
for Help.
Click
or
for Alarm History.
Safety Chain – Indicates if the safety chain circuit trips.
RTU Open v3
Installation and Start-up Guide
Performance
Alarms
104
Range
R:
__ hr
R:
0 to 100%
R:
0 to 100%
R:
0 to 100%
R:
0 to 100%
R:
0 to 100%
R:
0 to 100%
R:
__°F/C
R:
__°F/C
Range
R:
Normal/Alarm