Appendix C: RTU Open Points/Properties on the Equipment Touch

Setpoints - Equipment Touch

Navigation:
Equipment Touch:
Point Name/Description
Occupied Heating – Green
The heating setpoint the controller maintains while in occupied mode.
Occupied Cooling – Green
The cooling setpoint the controller maintains while in occupied mode.
Unoccupied Heating – Gray
The heating setpoint the controller maintains while in unoccupied mode.
Unoccupied Cooling – Gray
The cooling setpoint the controller maintains while in unoccupied mode.
Optimal Start Type – The method used to change from unoccupied to occupied setpoint.
Options:
None – Unit will not change to occupied setpoint until the scheduled time or the unit goes into an
occupied mode. Setpoints do not ramp, but change immediately from unoccupied to occupied
values.
Temp Compensated – Unit changes to occupied setpoints at a variable time prior to the occupied
time, which is calculated by the current difference between space temperature and the
appropriate heating or cooling setpoint. At that time, the setpoints do not ramp, but change
immediately from unoccupied to occupied values.
Learning Adaptive Start – Unit gradually changes to occupied setpoints by adjusting the
unoccupied setpoints over a specified period of time to achieve the occupied setpoint by the time
scheduled occupancy begins.
Heat Start K factor (min/deg) – If Optimal Start Type is Temp Compensated, this is the time in
minutes per degree that the equipment starts before the occupied period when the space
temperature is below the occupied heating setpoint (including any setpoint offset).
Cool Start K factor (min/deg) – If Optimal Start Type is Temp Compensated, this is the time in
minutes per degree that the equipment starts before the occupied period when the space
temperature is above the occupied cooling setpoint (including any setpoint offset).
RTU Open v3
Installation and Start-up Guide
Setpoints
100
Default/Range
D:
70°F (21.1°C)
R:
40 to 90°F
(4.4 to 32.2°C)
D:
76°F (24.4°C)
R:
55 to 99°F
(12.7 to 37.2°C)
D:
55°F (12.7°C)
R:
40 to 90°F
(4.4 to 32.2°C)
D:
90°F (32.2°C)
R:
45 to 99°F
(7.2 to 37.2°C)
D:
Temperature
Compensated
R:
None
Temperature
Compensated
Learning
Adaptive
D:
15.00
R:
0 to 99
D:
15.00
R:
0 to 99
CARRIER CORPORATION ©2019
All rights reserved