To wire an enthalpy switch (differential) to the controller
Wiring diagram for optional enthalpy sensor mounted in the return air for differential enthalpy:
Wiring a status switch
Filter - Part #CRSTATUS005A00 or field-supplied
Fan status - Part #CRSTATUS005A00 or field-supplied
Filter and/or fan status switches may be installed to provide a Dirty Filter indication or Fan Running status.
Wiring specifications
Cable from sensor to controller:
Maximum length:
RTU Open v3
Installation and Start-up Guide
If <100 ft (30.5 meters)
If >100 ft (30.5 meters)
500 feet (152 meters)
37
Installing the RTU Open
22 AWG, unshielded
22 AWG, shielded
CARRIER CORPORATION ©2019