Wiring A Status Switch - Carrier RTU Open v3 Installation And Startup Manual

Hide thumbs Also See for RTU Open v3:
Table of Contents

Advertisement

To wire an enthalpy switch (differential) to the controller
Wiring diagram for optional enthalpy sensor mounted in the return air for differential enthalpy:

Wiring a status switch

Filter - Part #CRSTATUS005A00 or field-supplied
Fan status - Part #CRSTATUS005A00 or field-supplied
Filter and/or fan status switches may be installed to provide a Dirty Filter indication or Fan Running status.
Wiring specifications
Cable from sensor to controller:
Maximum length:
RTU Open v3
Installation and Start-up Guide
If <100 ft (30.5 meters)
If >100 ft (30.5 meters)
500 feet (152 meters)
37
Installing the RTU Open
22 AWG, unshielded
22 AWG, shielded
CARRIER CORPORATION ©2019
All rights reserved