PROCESS TEMP CONTROL MODE #2
Capacity control setpoint
Upper proportional band
Upper dead band
Upper cycle time
Lower proportional band
Lower dead band
Lower cycle time
Autocycle start temp
Autocycle start delay
Autocycle stop temp
Autocycle stop delay
Low process temp stop load
Low process temp force unload
Low process temp alarm
Low process temp alarm delay
Low process temp shutdown
Low process temp shutdown delay
Low suction pressure stop load
Low suction pressure force unload
Low suction pressure alarm
Low suction pressure alarm delay
Low suction pressure shutdown
Low suction pressure shutdown delay
DISCHARGE PRESSURE CONTROL MODE #1
Capacity control setpoint
Upper proportional band
Upper dead band
Upper cycle time
Lower proportional band
Lower dead band
Lower cycle time
Autocycle start pressure
Autocycle start delay
Autocycle stop pressure
Autocycle stop delay
Low suction pressure stop load
Low suction pressure force unload
Low suction pressure alarm
Low suction pressure alarm delay
Low suction pressure shutdown
Low suction pressure shutdown delay
** based on maximum discharge pressure setting in factory setup.
FRICK QUANTUM COMPRESSOR CONTROL PANEL
MAINTENANCE
setting
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
setting
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
______
default
40°F
4°F
1°F
4 sec.
4°F
1°F
4 sec.
45°F
1 min.
36°F
1 min.
35°F
34°F
33°F
3 sec.
32°F
3 sec.
10 psig
5 psig
2 psig
3 sec.
0 psig
3 sec.
default
150 psig
5 psig
1 psig
3 sec.
5 psig
1 psig
3 sec.
160 psig
1 min.
140 psig
1 min.
10 psig
5 psig
2 psig
3 sec.
0 psig
2 sec.
S90-010 M
Page 31
range
-238 - 302°F
0 - 20 °F
0 - 10°F
0 - 60 sec.
0 - 20 °F
0 - 10°F
0 - 60 sec.
-238 - 302°F
0 - 60 min.
-238 - 302°F
0 - 60 min.
-238 - 302°F
-238 - 302°F
-238 - 302°F
0 - 60 sec.
-238 - 302°F
0 - 60 sec.
30" - 135 psig
30" - 135 psig
30" - 135 psig
0 - 60 sec.
30" - 135 psig
0 - 60 sec.
range
0 - 350** psig
0 - 20 psig
0 - 10 psig
0 - 60 sec.
0 - 20 psig
0 - 10 psig
0 - 60 sec.
0 - 350** psig
0 - 60 min.
0 - 350** psig
0 - 60 min.
30" - 135 psig
30" - 135 psig
30" - 135 psig
0 - 60 sec.
30" - 135 psig
0 - 60 sec.