® S90-560 M (AUG 07) FRICK QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL Page 2 MAINTENANCE TABLE OF CONTENTS INTRODUCTION TO THE QUANTUM™ LX CONDENSER/VESSEL CONTROL SYSTEM ........4 Quantum™ LX Control Panel Enclosure ......................4 Condenser And Vessel Panels..........................4 Operator Interface (Optional)..........................4 QUANTUM™...
Page 3
RECOMMENDED SPARE PARTS ......................... 54 INDEX ..................................55 THE FOLLOWING PUBLICATIONS ARE AVAILABLE Indicates an imminently hazardous ® DANGER situation which, if not avoided, will FROM THE FRICK WEBSITE frickcold.com result in death or serious injury. ® S90-560 CS Frick Quantum™ LX Condenser/Vessel Control...
Additional capable of Ethernet access, which can be viewed remotely information about the power supply is ® through any web browser, or the optional Frick Operator located under the POWER SUPPLY section Interface Panel. found later in this manual.
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 5 QUANTUM™ LX CONTROL PANEL The following pictorial shows front the Control Panel • Display portion of the unit, and shows the following components: • Keypad •...
® S90-560 M (AUG 07) FRICK QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL Page 6 MAINTENANCE CONDENSER PANEL The following two pictorials represent the Condenser • Digital and Analog control panel. The first of these pictorials contain the following • Fuses and circuit breakers components: •...
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 7 PANEL VESSEL The following two pictorials represent the Vessel panel. • Fuses and circuit breakers The first of these pictorials contain the following • HOA Modules.
® S90-560 M (AUG 07) FRICK QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL Page 8 MAINTENANCE POWER SUPPLIES FOR THE QUANTUM™ LX CONTROL PANEL AND CONDENSER/VESSEL PANELS If the voltages from the power supply are within the DESCRIPTION acceptable ranges, then measure them at the Quantum™...
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 9 CONDENSER/VESSEL PANEL STANDARD POWER If the voltages from the power supply are within the acceptable ranges, then measure them at the last I/O board in the daisychain, as shown below: The Condenser and Vessel Panels both utilize the +5 VDC, +12 VDC and –...
Because of the ever-increasing speed, memory ® and control circuits will be the result of a wiring fault, a features, and power of microprocessors, Frick will blown fuse, faulty I/O module or failure of a peripheral continue to introduce the latest advancement in control such as a solenoid coil or a pressure microprocessor control technology.
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 11 main processor board is not starting). Unfortunately, Install the modified replacement board into this description is usually vague and only means that the panel. nothing is showing on the web browser or the optional Operator Interface Panel.
Page 12
® S90-560 M (AUG 07) FRICK QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL Page 12 MAINTENANCE USB Connector +5VDC (Depending on board version, RET / GND USB could be located in either of Power RET / GND these to places). Cable +12VDC...
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 13 Note: There are duplicate numbers for the links on the processor (larger) board and the communications (smaller) board. If you must make a change to a jumper (link), then ensure that you modify the correct link.
The associated power/communications harness will only be plugged The Frick Condenser/Vessel control system utilizes into one of these connectors. Take the red (positive) up to two Digital, and one Analog Boards. To connect probe of the DVM and carefully insert the end into the all of these boards together so that the Quantum™...
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 15 Set the DVM to read DC, and set the proper range. Never plug a 120 Volt Input module into a 240 Volt The voltage reading must read a minimum of +5.0 system, and vice-versa.
• connected boards. If a board has been removed, a the Frick Service Department. communication error shutdown will be issued until this If the LED is on when it should be, check for key is selected.
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 21 DIGITAL BOARD SETTINGS COMMUNICATIONS SETTINGS The following table is to be used when configuring the Quantum™ for external communications. 120 ohm long communications line termination. out* No termination.
MAINTENANCE ANALOG BOARD OVERVIEW ANALOG BOARD DESCRIPTION The Frick Quantum™ LX Condenser/Vessel control The Analog Board is actually a small microprocessor panel is capable of reading external analog devices, board and is programmed to control analog outputs, such as temperature probes and pressure sensors. It...
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 23 positions of one row, are internally daisy-chained on Vdc. The Power-I/O harness will have an associated each I/O board, to continue the voltages and signals voltage drop at each board connection. As an to the adjacent row.
® S90-560 M (AUG 07) FRICK QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL Page 24 MAINTENANCE ANALOG OUTPUTS find a short to earth problem is to disconnect all the sensor plugs and ohm out each plug screw terminal to earth for open (infinite) impedance. All sensors should An Analog Output is the portion of the hardware that read open to earth.
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 27 ANALOG BOARD SETTINGS COMMUNICATIONS The following table is to be used when configuring the Quantum™ for external communications. 120 ohm long communications line termination. Out * No termination.
® S90-560 M (AUG 07) FRICK QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL Page 28 MAINTENANCE SERVICE SCREENS SERVICE – Communications Log SCREEN NAME: Service – Communications Log. Service… ACCESSING: Communications Log DESCRIPTION: This screen allows the technician to view the status of all communications ports.
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 29 SERVICE – Communications Loop-Back Test SCREEN NAME: Service – Communications Loop Back Test. Service ACCESSING: Communications Loop Back Test DESCRIPTION: This screen allows the user to test the integrity of each of the communications channels, by using a Loop-Back cable.
® S90-560 M (AUG 07) FRICK QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL Page 30 MAINTENANCE SERVICE – Diagnostics SCREEN NAME: Analog I/O. ACCESSING: Service… Diagnostics DESCRIPTION: The Diagnostics screen has been provided as a way for the user to test the Ethernet connection.
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (AUG 07) MAINTENANCE Page 31 SERVICE – Software Maintenance SCREEN NAME: Software Maintenance. Service… Software Maintenance ACCESSING: DESCRIPTION: This screen allows the technician to perform system software maintenance. The following selections have been provided:...
Page 32
® S90-560 M (AUG 07) FRICK QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL Page 32 MAINTENANCE • After the file has been written or updated, the dialog boxes will disappear, and you can either exit, or continue with another function. Delete Setpoints – Use this option to delete the setpoints and custom text for a particular unit.:...
® FRICK QUANTUM™ LX CONDESNER/VESSEL CONTROL PANEL S90-560 M (JUL 07) MAINTENANCE Page 33 MISCELLANEOUS MAINTENANCE SCREENS About SCREEN NAME: Sequencing. ACCESSING: About DESCRIPTION: The About screen shows the Analog and Digital boards that have been detected. If a board has lost communications, a shutdown will be issued.
PLC or Opto22 panel. □ In the event it becomes necessary to erase the ® Check that you are using the Frick recommended systems setpoints, use the following procedure: communications cable. See manual to match Ensure that the existing setpoints are proper cable with type of communications (i.e.,...
® S90-560 M (AUG 07) FRICK QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL Page 54 MAINTENANCE RECOMMENDED SPARE PARTS Quantum™ LX Control Panel Part Number Description Control Power 639A0185H10 2-Pos. Selector Switch (Control Power) 639A0185H31 Normally Open Contact Block (for Control Power Switch)