S90-010 M
Page 20
ANALOG BOARD #1
Input Channel #1 – Suction Temperature
Out
0-5 volt input
J1
1-2
4-20 ma. input
2-3*
ICTD input (standard setting)
Input Channel #2 - Discharge Temperature
Out
0-5 volt input
J2
1-2
4-20 ma. input
2-3*
ICTD input (standard setting)
Input Channel #3 - Oil Temperature
Out
0-5 volt input
J3
1-2
4-20 ma. input
2-3*
ICTD input (standard setting)
Input Channel #4 – Oil Separator Temperature
Out
0-5 volt input
J4
1-2
4-20 ma. input
2-3*
ICTD input (standard setting)
Input Channel #5 – Leaving Process Temperature**
Out
0-5 volt input
J5
1-2
4-20 ma. input
2-3*
ICTD input (standard setting)
Input Channel #6 - Oil Pressure
out*
0-5 volt input (standard setting)
J6
1-2
4-20 ma. input
2-3
ICTD input
Input Channel #7 - Oil Filter Pressure**
Out*
0-5 volt input (standard setting)
J7
1-2
4-20 ma. input
2-3
ICTD input
Input Channel #8 - Discharge Pressure
Out*
0-5 volt input (standard setting)
J8
1-2
4-20 ma. input
2-3
ICTD input
Input Channel #9 – Suction Pressure
Out*
0-5 volt input (standard setting)
J9
1-2
4-20 ma. input
2-3
ICTD input
Input Channel #10 - Balance Piston Pressure**
Out*
0-5 volt input (standard setting)
J10
1-2
4-20 ma. input
2-3
ICTD input
Input Channel #11 - System Discharge Pressure**
Out*
0-5 volt input (standard setting)
J11
1-2
4-20 ma. input
2-3
ICTD input
Input Channel #12 - Remote Capacity Control Setpoint**
Out
0-5 volt input
J12
1-2*
4-20 ma. Input (standard setting)
2-3
ICTD input
FRICK QUANTUM COMPRESSOR CONTROL PANEL
MAINTENANCE
Input Channel #13 - Remote Slide Valve Position**
Out
0-5 volt input
J13
1-2*
4-20 ma. Input (standard setting)
2-3
ICTD input
Input Channel #14 - Slide Valve**
J14
In
All other input types (0-5 volt, 4-20 ma., ICTD)
out*
Slide valve potentiometer input. (std setting)
J15
out*
0-5 volt input (standard setting)
1-2*
4-20 ma. Input
2-3
ICTD input
J16
in
All other input types (0-5 volt, 4-20 ma., ICTD)
out*
Slide valve potentiometer input. (std setting)
Input Channel #15 - Slide Stop**
J17
in†
All other input types (0-5 volt, 4-20 ma., ICTD)
out*
Slide stop potentiometer input. (std setting)
J18
out*
0-5 volt input (standard setting)
1-2†
4-20 ma. Input
2-3†
ICTD input
J19
in†
All other input types (0-5 volt, 4-20 ma., ICTD)
out*
Slide valve potentiometer input. (std setting)
Input Channel #16 - Motor Amps
0-5 amp CT input*
out
0-5 volt input
4-20 ma. input
ICTD input
Output Channel #1 - Future
J26
1-2
0-20 ma. output.
2-3
4-20 ma. output
J39
1-2
4-20 ma. output
2-3
0-20 ma. Output
IC's
install
U15 & U7 Connect to P10 terminals 1 & 2
Output Channel #2 - Future
J25
1-2
0-20 ma. output.
2-3
4-20 ma. output
J40
1-2
4-20 ma. output
2-3
0-20 ma. output
IC's
install
U15 & U6 Connect to P10 terminals 3 & 4
Output Channel #3 - Slide Valve Position \ Capacity**
J24
1-2
0-20 ma. output.
2-3*
4-20 ma. output (standard setting)
J41
1-2*
4-20 ma. output (standard setting)
2-3
0-20 ma. output
IC's
install
U15 & U5 Connect to P10 terminals 5 & 6
Output Channel #4 – Remote Control Setpoint**
J23
1-2
0-20 ma. output.
2-3*
4-20 ma. output (standard setting)
J42
1-2*
4-20 ma. output (standard setting)
2-3
0-20 ma. output
IC's
install
U15 & U4 Connect to P10 terminals 7 & 8
** If applicable
† RWF compressor standard setting
Note: IC's must also be installed in order to enable the
analog output options. U15 along with at least one IC
(U4,U5,U6 or U7) installed will enable the channel.
J20
J21
J22
out
in
(std)
(std)
(std)
out
out
out
in
out
out
out
in
out
Need help?
Do you have a question about the QUANTUM and is the answer not in the manual?
Questions and answers