Any modification to these control settings is the sole responsibility of ® the user/owner and Frick disclaims any liability for the consequences of these modifications. It is possible that the modification of these settings may cause improper operation and performance that results in property damage, personal injury or death.
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 4 OPERATION KEYS AND KEY FUNCTIONS DECIMAL [.] - The decimal point is used when entering a KEYPAD KEYS decimal value in a data field. Following is a list of the labeled keypad keys and the...
Any modification to these control settings adjustable setpoint values, this positions the cursor at ® is the sole responsibility of the user/owner and Frick the first data entry field. (See To Change Setpoints disclaims any liability for the consequences of these for more information.)
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 6 OPERATION accessed performed only Factory INITIAL SETUP PROCEDURE Representative or Distributor. Panel Setup is performed first. Panel Setup is Calibrate the control devices. used to setup panel features and options that later can be changed by an operator.
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 7 “AIR HANDLING UNIT OVERVIEW” SCREEN – SCREEN KEY SET Following are the screen key selections for the "Air · Selectable Options Handling Unit Overview" screen: · Screen Setup ·...
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 8 OPERATION UNIT SELECTED - "OPERATING STATUS" SCREEN Operator Selection Keys Date and Time Unit Name Screen Title Air Handling Unit Data Box Analog Readings Box Alarm Status Demand Output...
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 9 ANALOG READINGS BOX: OPERATOR SELECTION KEYS The following analog input readings are possible. Following are the screen key selections for the They are shown if they were enabled during the "Operating Status"...
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 10 The following outputs are shown in the first block (if they · Suction were enabled during the board setup): · Hot Gas · Bleed · Supply Fan Motor ·...
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 11 MAIN MENU SELECTION - "ALARMS/SHUTDOWNS" SCREEN following "Alarms/Shutdowns" screen To clear or reset the "Alarms/Shutdowns" screen selection keys: and turn off any alarm annunciation device, from the screen press the [Clear Alarms] key. This ·...
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 12 OPERATION MAIN MENU SELECTION - "CONTROL SETUP" (1) SCREEN This screen is accessible from the Main Menu screen percent setting for the Outside Air Dampers. The when Security is set to either "Moderate Access" or "No range for the Outside Air Dampers is 100% for Access".
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 13 MAIN MENU SELECTION - "CONTROL SETUP" (2) SCREEN This screen is accessible from the Main Menu screen The following are the "Control Setup" screen selections: when Security is set to "Full Access". These setpoints ·...
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 14 OPERATION CONTROL SETUP - “COOLING CONTROL SETUP” SCREEN Cooling Control Setpoints used maintain Together they keep the unit from rapidly cycling on and temperature in either Process or Cleanup Mode. A PID off.
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 15 output is 75%, at 37 °F the output is 50%, at 36 °F the output rises above 25% Cooling Stage #1 is turned on. If the PID output continues to rise and reaches 50%, output is 25% and below 35 °F the PID output drops to...
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 16 OPERATION CONTROL SETUP - “EXHAUST CONTROL SETUP” SCREEN The Exhaust Setpoints control the two exhaust fans on The Exhaust Demand Value is the current Outside Air the unit. The Exhaust Demand Value, which is displayed...
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 17 CONTROL SETUP - “DAMPER CONTROL SETPOINT” SCREEN The Damper Setpoints control the Outside Air Dampers the Economizer Switchover Setpoint, the Economizer flag and the Economizer function of the unit. The Minimum...
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 18 OPERATION CONTROL SETUP - “HEAT PROFILE CONTROL” SCREEN CONTROL SETUP - “SAFETY SETPOINTS” SCREEN These alarm setpoints are important for safe operation. · Ammonia Shutdown Delay - Amount of time...
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 19 ANALOG CALIBRATION - "MAIN MENU" SCREEN The following warning message is displayed when actions. At the very minimum, prior to any such action, selecting this menu: you should have thoroughly read and understood all manuals and literature accompanying the unit.
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 20 OPERATION ANALOG CALIBRATION - "PRESSURE CALIBRATION" SCREEN A screen key exists for each of the displayed analog Room Differential · readings. This screen shows a pressure gauge and the...
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 21 ANALOG CALIBRATION - "TEMPERATURE CALIBRATION" SCREEN A screen key exists for each of the displayed analog · Discharge Air readings. This screen shows a thermometer and the ·...
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 22 OPERATION ANALOG CALIBRATION - "OTHER CALIBRATION" SCREEN A screen key exists for each of the displayed analog · Exhaust Damper 2 readings. This screen shows a meter and the current ·...
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 23 PANEL SETUP - “PANEL SETUP” SCREEN The current setup is shown at the Panel Setup selection. [Change Degrees] - The following screen keys The following Panel Setup screens can be selected: are provided: ·...
Page 24
· ScreenSaver - A toggle key is provided: the screen and the following selections are provided: [Disable] - Disables the screen saver. · [Standard Screen] - The Frick ® "Blue" screen [Enable] - Enables the screen saver. When color is used.
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 25 "SECURITY SETUP" SCREEN Security can be setup to allow different operators different Change Setpoints from Keypad: access rights to setpoints. If access is presently denied Enabled when an operator selects to [Change Setpoints] then a...
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 26 OPERATION PANEL STATUS - "REAL TIME TRENDING" SCREEN Real time trending saves 900 recordings of the data items [Trending View] Accesses the Real Time from the Operating Status screen. The data is stored in Trending screen for viewing the data in a graphical RAM memory.
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 27 PANEL STATUS - "REAL TIME TRENDING" SCREEN – DATA LOG VIEW The following screen command keys are provided: · Unit 2 Exhaust 2 · Unit 2 Ammonia Will cause the most recent page of [Goto Start] ·...
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 28 OPERATION PANEL STATUS - "REAL TIME TRENDING" SCREEN – TRENDING VIEW This screen will show in a graphic format, the same data numbers that appear along the vertical line show the that appears on the Data Log view, shown on the previous actual value of the reading taken.
® ® FRICK QUANTUM™ ACUair CONTROL PANEL S90-500 O OPERATION Page 29 PANEL STATUS - "HISTORY TRENDING" SCREEN History trending saves 2000 recordings of the data items The following screen command keys are provided: from the Operating Status screen. History data is stored...
® ® S90-500 O FRICK QUANTUM™ ACUair CONTROL PANEL Page 30 OPERATION Alarms/Shutdowns Messages Auxiliary 3 Alarm/Shutdown Following is the alphabetical listing of all the possible Coil Air Temp. Sensor fault alarms: Damper Pos. Sensor fault Ammonia Alarm Defrost Input Fault to On...