Fli Index And User Names; Master Trip Output; Register Configuration; Miscellaneous Settings - ABB DPU 1500R Instruction Book

Distribution protection unit
Table of Contents

Advertisement

9/99
Table 5-5. Communications Settings (Password Protected)
Setting
Unit Address
Front RS232 Port:
Baud Rate
Frame
Rear Port RS232 :
Baud Rate*
Frame
Rear Port RS485 :
Baud Rate*
Frame
Rear Port INCOM Baud Rate*
Rear Port IRIG-B Enable*
Network Parameters*
Network Modes*
* Check catalog number for available communications port options. Network parameters and
network modes are specific settings designed for various SCADA protocols.
In addition to the Tables 5-1 through 5-5, under the "Change Settings" Menu, the following settings are also available:

FLI Index and User Names

This allows the user to set up a table of Logical Inputs that can be "forced" via the Operations Menu. See Section 8 for
details.

Master Trip Output

The user has the ability to allow only certain protective elements to operate the Master Trip Output Contact (terminals
29 and 30). See Section 6 for more details.

Register Configuration

For use with Modbus Communications. Contact Factory for details.

Miscellaneous Settings

Under the Miscellaneous Settings Menu, you will find the following:
User Display Message-
Programmable Input.
Interfacing with the Relay
Range
3 hexadecimal characters (0-9 & A-F)
300, 1200, 2400, 4800, 9600
N,8,1 or N,8,2
300, 1200, 2400, 4800, 9600, 19200
N,8,1; E,8,1; ODD,8,1; N,8,2; E,7,1;
ODD,7,1; N,7,2
300, 1200, 2400, 4800, 9600, 19200
N,8,1; E,8,1; ODD,8,1; N,8,2; E,7,1;
ODD,7,1; N,7,2
1200, 9600
Disable or Enable
0 to 250
Disable or Enable
For use with the User Display Input (UDI)
The user can type a 4 line message here. When UDI is
asserted, this message will blink on the MMI.
website:www.abb.com/papd
ABB Distribution Protection Unit 1500R
Default
001
9600
N,8,1
9600
N,8,1
9600
N,8,1
9600
Disable
0
Disable
5-23