Table 5-2. Configuration Settings (Password Protected)
Setting
Phase CT Ratio
VT Ratio
VT Connection (VT Conn:)
Positive Sequence Reactance/Mile (km)
Positive Sequence Resistance/Mile (km)
Zero Sequence Reactance/Mile (km)
Zero Sequence Resistance/Mile (km)
Line Length
Trip Failure Time
Close Failure Time
Phase Rotation (Phase Rotate:)
Protection Mode (Prot. Mode:)
Reset Mode - 51(3I>)/46 (Insc>)
Alternate 1 Settings (Alt1 Set)
Alternate 2 Settings (Alt2 Set)
Multiple Device Trip Mode* (MDT)
Cold Load Time Mode
79V (O->IU<)Time Mode
Volt Display
Zone Sequence
Target Display Mode
Remote Edit = (Remote Edit) †
Local Edit (Comm Ports Only) ††
Meter Mode (WHr Display)
LCD Light
Unit Identification (ID)
Demand Meter Constant
(Demand Minutes)
LCD Contrast
Change Test Password
SE CT Ratio ⊗
SE V0 PT Ratio ⊗
*
When the Multiple Device Trip Mode is enabled, the reset mode
automatically goes to Instantaneous setting and cannot be
changed.
SEF model
Interfacing with the Relay
Range
1 - 2000
1 - 2000
69 V or 120 V Wye (Star), phase to ground;
120 V or 208 V Delta, phase to phase
0.001 to 4 Ohms/Mile (km)
0.001 to 4 Ohms/Mile (km)
0.001 to 4 Ohms/Mile (km)
0.001 to 4 Ohms/Mile (km)
0.1 to 125 miles (km)
5 to 60 cycles
18 to 999 cycles
ABC or ACB
Fund. or RMS
Instant (2 cycles) or Delayed
Enable or Disable
Enable or Disable
Disable or Enable
Seconds or Minutes
Seconds or Minutes
Vln or Vll
Disable or Enable
Last or All (faults)
Enable or Disable
Enable or Disable
kWHr or MWHr (6 Digits)
On or Time Out (5 Minutes)
(15 alphanumeric characters)
5, 15, 30, or 60 minutes
0 to 63
4 Alphanumeric characters
1 to 2000
1 to 2000
website:www.abb.com/papd
ABB Distribution Protection Unit 1500R
Default
Step Size
1
1
100
100
1
120V Wye
-
0.001
0.001
0.001
0.001
0.001
0.001
0.001
0.001
0.1
20
18
1
18
1
-
ABC
-
Fund.
-
Instant
-
Enable
-
Enable
-
Disable
-
Seconds
-
Seconds
-
Vln
-
Disable
-
Last
-
Enable
-
Enable
-
kWHr
-
On
-
DPU1500R
-
15
1
16
-
4 blank spaces
1
1
1
1
† Remote edit appears only in MMI display.
††Local edit appears only in the WinECP display.
5-21