The pinout for the DB9 port for option 8 is as follows:
Pin Signal
1
RS485 (+)
2
RS485 (–)
3
Direction (+) RTSA
4
Direction (–) RTSB
7
RS485 COMMON
8
+5VDC at 100ma

Communication Protocols

The Select Options Table shows the communication protocols and the respective hardware port assignments that are
currently available.
The "Standard" protocol referenced throughout this publication refers to an ABB DPU1500R specific 10 byte ASCII
oriented communication protocol. This protocol is standard for COM 1 and is selectable for other rear ports as per the
Select Options Table. The Windows External Communication Program (WinECP) is provided at no charge with the
relay. The protocol document is available on request.
Product specific protocol documents are available from the factory upon request.
DNP 3.0 Protocol
Modbus Protocol

RTU Emulation

Also available are external RTU Emulation devices that provide a pre-engineered interface between the DPU1500R
and a SCADA host. Contact the factory for additional information on the ORION unit.
Modbus
®
is a registered trademark of Modicon, Inc.
INCOM™ is a registered trademark of Cutler Hammer Corporation.
website:www.abb.com/papd
12-8