ABB Distribution Protection Unit 1500R
Timing Curves
Time Overcurrent Curve Equation
Table 1-12. Constants for IEC Time Overcurrent Characteristics
1-10
IEC
K
Trip Time =
α
G
– 1
G
b
Reset Time = instantaneous
G
= multiples of pickup current
G
b
Time multiple range 0.05 to 1.0 in steps of 0.05
Curve
K
Extremely Inverse
80.0
Very Inverse
13.5
Inverse
0.14
Long Time Inverse
120.0
website:www.abb.com/papd
x time multiple
α
2.0
1.0
0.02
1.0