Table 1-10. 46 (Insc>) Characteristics
51P Parameter
Pickup for 5 ampere model
Pickup for 1 ampere model
Time Overcurrent Curves **
ANSI
IEC
** See model number for applicability
*** Optional
The 46 element is disabled in the factory default settings
1-8
Range/Curve
1 to 12 amperes
0.2 to 2.4 amperes
Inverse
Very Inverse
Extremely Inverse
Long Time Inverse
Long Time Very Inverse
Long Time Ext. Inverse
Short Time Inverse
Definite Time
Recloser Curve
Inverse
Very Inverse
Extremely Inverse
Long Time Inverse
User Prog. Curve #1 ***
User Prog. Curve #2 ***
User Prog. Curve #3 ***
.
website:www.abb.com/papd
Time Dial
Increment
0.1 ampere
0.02 ampere
1 to 10
0.1
1 to 10
0.1
1 to 10
0.1
1 to 10
0.1
1 to 10
0.1
1 to 10
0.1
1 to 10
0.1
0 to 10
0.1
1 to 10
0.1
0.05 to 1.0
0.05
0.05 to 1.0
0.05
0.05 to 1.0
0.05
0.05 to 1.0
0.05
1 to 10
0.1
1 to 10
0.1
0 to 10
0.1
9/99