ABB DPU 1500R Instruction Book page 74

Distribution protection unit
Table of Contents

Advertisement

ABB Distribution Protection Unit 1500R
Table 5-1. Primary, Alternate 1 and Alternate 2 Settings (Password Protected) (Continued)
Function
50N-2 ⊗
(IO / >)
50N-3
(IN>>3)
79
(O->I)
79-1
(O->I1)
79-2
(O->I2)
79-3
(O->I3)
79-4
(O->I4)
79-5
(O->I5)
79-CO (O->I-CO)
Cold Load Time
2-Phase 50P
(3I>>)
27
(U<)
79V
(O->IU<)
* Directional SEF Model Only
⊗ SEF Model
5-20
Setting
Select
Disable, Standard, SEF, Directional SEF
SEF Pickup Amps ⊗
0.005 to 0.200 A
Delay ⊗
0.5 to 180.0 seconds
Torque Angle*
0 to 355
Selection
Disable or Enable
0.5 to 20 times
Pickup X 51N
51N pickup setting
Reset Time
3 to 200 seconds
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
Select
50N-3 (Enable, Disable, or Lockout for each)
Open Time
0.1 to 200 seconds or Lockout
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
Select
50N-3 (Enable, Disable, or Lockout for each)
Open Time
0.1 to 200 seconds or Lockout
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
Select
50N-3 (Enable, Disable, or Lockout for each)
0.1 to 200 seconds or Lockout
Open Time
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
Select
50N-3 (Enable, Disable, or Lockout for each)
0.1 to 200 seconds or Lockout
Open Time
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
Select
50N-3 (Enable, Disable, or Lockout for each)
Open Time
Lockout
Cutout Time
1 to 200 seconds or Disable
0 to 254 seconds/minutes or Disable
2Phase 50P Trip
Disable or Enable
Select
Disable or Enable
Pickup Volts
10 to 200 volts AC
Time Delay
0 to 60 seconds
Voltage Select
Disable or Enable
Pickup Volts
10 to 200 volts AC
Time Delay
4 to 200 seconds
website:www.abb.com/papd
Range
9/99
Step Size
Default
Disable
-
0.0005
0.1
-
-
5
Disable
0.1
-
1
10.00
50-P Enable
51-N Enable
50N-1 Enable
Lockout
0.1
-
0.1
-
-
-
0.1
-
-
0.1
-
-
1
Disable
1
Disable
Disable
Disable
1
-
1
-
1
-
-
1