ABB DPU 1500R Instruction Book page 105

Distribution protection unit
Table of Contents

Advertisement

ABB Distribution Protection Unit 1500R
Table 7-2 (cont.)
Ext Trip Enabled
Ext Trip Disabled
Event Cap 1 Init
Event Cap 1 Reset
Event Cap 2 Init
Event Cap 2 Reset
Wave Cap Init
Wave Cap Reset
Ext Close Enabled
Ext Close Disabled
52a Closed
(
)
XO
52a Opened
(
)
XO
52b Closed
(
)
XI
52b Opened
(
)
XI
46 Unit Enabled
(
)
Insc>
46 Unit Disabled
(
)
Insc>
CRI Input Closed
CRI Input Opened
7-12
Indicates that the programmable input "Open" was asserted. This record indicates the state of the
programmable input "Open" only. It does not imply an actual breaker trip.
Indicates that the programmable input "Open" was de-asserted.
Indicates that the programmable input "ECI1" was asserted and an event capture taken. The data
from the event is stored in the Fault Records.
Indicates that the programmable input "ECI1" was de-asserted.
Indicates that the programmable input "ECI2" was asserted and an event capture taken. The data
from the event is stored in the Fault Records.
Indicates that the programmable input "ECI2" was de-asserted.
Indicates that the programmable input "WCI" was asserted and an oscillographic record stored. The
data from the event is stored in the Waveform Capture Records.
Indicates that the programmable input "WCI" was de-asserted.
Indicates that the programmable input "Close" was asserted. This record indicates the state of the
programmable input "Close" only. It does not imply an actual breaker close.
Indicates that the programmable input "Close" was de-asserted.
Indicates the state of the programmable logic input "52A". This record indicates the state of the
programmable input "52A" only. It does not imply an actual breaker state. The "52A Closed" record
indicates that the "52A" logical input was at a logical 1 at the time of the logging.
Indicates the state of the programmable logic input "52A". This record indicates the state of the
programmable input "52A" only. It does not imply an actual breaker state. The "52A Opened" record
indicates that the "52A" logical input was at a logical 0 at the time of the logging.
Indicates the state of the programmable logic input "52B". This record indicates the state of the
programmable input "52B" only. It does not imply an actual breaker state. The "52B Closed" record
indicates that the "52B" logical input was at a logical 1 at the time of the logging.
Indicates the state of the programmable logic input "52B". This record indicates the state of the
programmable input "52B" only. It does not imply an actual breaker state. The "52B Opened" record
indicates that the "52B" logical input was at a logical 0 at the time of the logging.
Indicates that the programmable input, "46" transitioned from a logical 0 to a logical 1, enabling the
negative sequence time overcurrent element if used. This log indicates the state of the "46" input
only.
Indicates that the programmable input, "46" transitioned from a logical 1 to a logical 0, disabling the
negative sequence time overcurrent element if used. This log indicates the state of the "46" input
only.
Indicates that the programmable input Clear Reclose and Overcurrent Counters, "CRI", transitioned
from a logical 0 to a logical 1. See Section 6, specifically the "CRI" input, for more details.
Indicates that the programmable input Clear Reclose and Overcurrent Counters, "CRI", transitioned
website:www.abb.com/papd
9/99
Records