[Device & Common]
2.5.2

Functions and operation examples

1. General type
X000
TS200
X000
Current
value
Y000
• The program of 100 ms/10 ms type timer of the FX
100 ms timers are changed to timers which operate based on the 10 ms base clock when the special
auxiliary relay M8028 is driven in the program.
M8000
RUN monitor
X003
1-second timer
2. Retentive type
X000
TS250
X002
t1
X001
Rete-
ntive
time
Current
value
Y001
X002
50
OUT_T
EN
ENO
TCoil
TC200
K123
TValue
Set value (constant)
A data register can
be specified instead.
Y000
1.23 sec
Set value
M8028
OUT_T
EN
ENO
TCoil
TC32
K100
TValue
OUT_T
EN
ENO
TCoil
TC250
K345
TValue
Set value (constant)
A data register can
be specified instead.
Y001
RST
EN
ENO
d
t2
t1 + t2 = 34.5 sec
Retentive time
Set value
When the drive input X000 of the timer T200
turns ON, the current value counter for T200
adds and counts clock pulses of 10 ms. When
the count value becomes equivalent to the set
value K123, the output contact of the timer turns
ON.
In other words, the output contact turns ON 1.23
seconds after the coil is driven.
When the drive input X000 turns OFF or when
the power is turned OFF, the timer is reset and
the output contact turns OFF.
, FX
, FX
0S
0
0N
When the drive input X001 of the timer T250
turns ON, the current value counter for T250
adds and counts clock pulses of 100 ms. When
the count value becomes equivalent to the set
value K345, the output contact of the timer turns
ON.
Even if the drive input X001 turns OFF or if the
power is turned OFF during counting, the timer
continues counting when the operation restarts.
The retentive operating time is 34.5 seconds.
TC250
When the reset input X002 turns ON, the timer is
reset and the output contact turns OFF.
2 Devices in Detail