Mitsubishi Electric MELSEC-Q Structured Programming Manual page 297

Hide thumbs Also See for MELSEC-Q:
Table of Contents

Advertisement

FXCPU Structured Programming Manual
[Device & Common]
2. On the "Ethernet Port" tab, click the "Open Setting" button.
On the "Ethernet Port Open Setting" dialog box, set the protocol, open system and others.
Up to four connections can be set up.
Set item
Protocol
Open System
Host Station Port No.
Destination IP Address
Destination Port No.
3. Click the "END" button to finish the setting and close the "Ethernet Port Open Setting"
dialog box.
Contents of setting
Select a protocol to be used.
Select the open system.
Set host station port No.
(This column is valid only when the selected open system is "MC
Protocol" or "Data Monitoring".)
Set destination IP address.
(This column is valid only when the selected protocol is "UDP" and
the selected open system is "MC Protocol".)
When this column is valid, "No Setting" is displayed in red.
Click "No Setting" to display the IP address setting dialog which
allows setting of the IP address.
When setting of the IP address is completed, the entered IP
address is displayed in blue.
Set destination port No.
(This column is valid only when the selected protocol is "UDP" and
the selected open system is "MC Protocol".)
6 Types and Setting of Parameters
6.6 Parameter setting by GX Works2
Setting range
Not Set, TCP, UDP
TCP:
Select "MELSOFT Connection",
"MC Protocol" or "Data Monitoring".
UDP:
The open system is fixed to "MC Protocol".
MC protocol:
1025 to 5548 or 5560 to 65534
Data monitoring:
80 (Default), 1025 to 5548 or 5560 to 65534
0.0.0.1 to 255.255.255.254 (decimal)