Mitsubishi Electric MELSEC-Q Structured Programming Manual page 259

Hide thumbs Also See for MELSEC-Q:
Table of Contents

Advertisement

FXCPU Structured Programming Manual
[Device & Common]
PLC
Error
operation
code
at error
occurrence
PLC/PP communication error [M8062(D8062)]
0000
-
No error
6201
Parity error, overrun error or framing error
6202
Communication character error
Continues
6203
Communication data sum check error
operation
6204
Data format error
6205
Command error
Parallel link communication error 1 [M8063(D8063)]
0000
-
No error
6301
Parity error, overrun error or framing error
6302
Communication character error
6303
Communication data sum check error
6304
Data format error
6305
Command error
Continues
6306
Monitoring timeout error
operation
6307 to
No error
6311
6312
Parallel link character error
6313
Parallel link sum check error
6314
Parallel link format error
Parameter error [M8064(D8064)]
0000
-
No error
6401
Program sum check error
6402
Memory capacity setting error
6403
Latched area setting error
Stops
operation
6404
Comment area setting error
6405
File register area setting error
6409
Other setting error
Contents of error
5.2 FX1S/FX1N/FX1NC/FX2N/FX2NC PLCs
Action
Confirm that the equipment connected to the programming panel
(PP) or programming connector is connected securely to the PLC.
This error may occur when a cable is disconnected and reconnected
while the PLC power is ON.
Inverter communication, computer link and programming:
Confirm that communication parameters are set correctly in
accordance with the application.
Simple N:N link, parallel link, etc.:
Confirm that the program is set correctly in accordance with the
application.
Confirm the wiring of communication cables.
Stop the PLC, and set the parameters correctly.
5 Errors
1
2
3
4
5
6
7
257

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-lMelsec-fFx3sFx3gFx3gcFx3u ... Show all

Table of Contents