4.2.11 Built-in analog variable potentiometers [D8030, D8031, D8013]

• Program for built-in analog variable potentiometers
Program values for built-in analog variable potentiometers are stored in the following special data registers
as numeric data within the range from 0 to 255 in accordance with the scale position.
Values received as numeric values can be specified as the indirectly specified value for a timer to provide
variable potentiometer type analog timers.
[Special data registers]
FX
, FX
1S
1N
VR1→D8030
VR2→D8031
[Example of basic circuit]
X003
Data register which stores
an analog variable potentiometer
value (integer in range from 0 to 255)
*1.
FX
-30M /E -2AD are not applicable to built-in analog variable potentiometers.
3S
230
*1
FX
, FX
, FX
PLC
3S
3G
D8013
OUT_T
EN
ENO
TCoil
TC10
D8030
TValue
(0 to 25.5 sec)
4 Operations of Special Devices (M8000 and later, D8000 and later)
4.2 Supplement of Special Devices (M8000 and later and D8000 and later)
, FX
PLC
0S
0
[Example of applied circuit]
M8000
RUN monitor
D8031
K2
X003
TC10
D0
The set value range can be changed
(to "32,767" maximum) by multiplying the contents of the
data register by "n".
Do not use D1 in other programs.
FX
PLC
0N
VR1→D8013(D8030)
VR2→D8031
MUL_E
EN
ENO
_IN
D0
_IN
[Value of D8031 (VR2)] 2
Transferred to (D1, D0)
OUT_T
EN
ENO
TCoil
TValue
(0 to 51 sec)