Bryant 579F User Manual page 77

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

OPTIONAL POWER EXHAUST
POWER REQUIREMENTS
AMPS AT
UNIT
230 V
SIZE
(2 Fans
Running)
1.40 Amps at
580F036-073
60 Hz
3.04 Amps at
580F090-151
60 Hz
LEGEND
MOCP — Maximum Overcurrent Protection
PERFORMANCE DATA (cont)
2500
2000
1500
1000
500
0
0
0.1
STATIC PRESSURE (in. wg)
HORIZONTAL POWER EXHAUST PERFORMANCE
2500
2000
1500
1000
500
0
0.05"
Static Pressure (in. wg)
BAROMETRIC RELIEF CAPACITY
30
25
20
15
10
5
0
0.1"
0.2"
Static Pressure (in. wg)
OUTDOOR AIR DAMPER LEAKAGE
Horizontal EconoMi$er IV and EconoMi$er2
Performance Data (580F036-151)
MOCP
230 VAC
460 VAC
575 VAC
15.0 amps 15.0 amps 15.0 amps
0.2
0.3
0.4
0.5
a48-6224
0.15"
0.25"
0.3"
0.4"
0.5"
EVAPORATOR-FAN MOTOR EFFICIENCY
UNIT 580F
036,048
060
072, 073
090-121
150, 151
*Single phase/three-phase.
NOTE: The EPACT (Energy Policy Act of 1992) regulates energy
requirements for specific types of indoor fan motors. Motors regulated
by EPACT include any general purpose, T-frame (three-digit, 143 and
larger), single-speed, foot mounted, polyphase, squirrel cage induction
motors of NEMA (National Electrical Manufacturers Association) design
A and B, manufactured for use in the United States. Ranging from 1 to
200 Hp, these continuous-duty motors operate on 230 and 460 volt,
60 Hz power. If a motor does not fit into these specifications, the motor
does not have to be replaced by an EPACT-compliant energy-efficient
motor. Variable-speed motors are exempt from EPACT compliance
requirements. Therefore, the indoor-fan motors for these units are
exempt from these requirements.
77
a48-6309
3-6 Ton
7 1/2 - 12 1/2 Ton
3-6 Ton
7 1/2 - 12 1/2 Ton
a48-6225
MOTOR EFFICIENCY (%)
75
74/84*
84
80
87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

581a581b581c580f