Electrical Data - Bryant 579F User Manual

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
579F
(3 Ph, 60 Hz)
Min
208/230
187
180
460
414
(15 Tons)
575
518
208/230
187
216
460
414
(18 Tons)
575
518
208/230
187
240
460
414
(20 Tons)
575
518
208/230
187
300
460
414
(25 Tons)
575
518
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent voltage
imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage

ELECTRICAL DATA

COMPRESSOR
No. 1
No. 2
Max
RLA LRA
RLA
LRA Qty Hp
253
28.8
195
28.8
195
508
14.7
95
14.7
95
633
10.8
80
10.8
80
253
30.1
225
28.8
195
508
15.5
114
14.7
95
633
12.1
80
10.8
80
253
37.8
239
30.1
225
508
17.2
125
15.5
114
633
12.4
80
12.1
80
253
41.0
350
37.8
239
508
21.8
158
17.2
125
633
17.3
125
12.4
80
OFM
IFM
FLA (ea)
Hp
FLA
3
0.5
1.7
3.7
10.5/11.0
3
0.5
0.8
3.7
4.8
3
0.5
0.8
3.0
3.9
3
0.5
1.7
5.0
15.8/15.8
3
0.5
0.8
5.0
7.9
3
0.5
0.8
5.0
6.0
2
1
6.6
7.5
25.0/25.0
2
1
3.3
7.5
13.0
2
1
3.4
7.5
10.0
2
1
6.6
10.0
28.0/28.0
2
1
3.3
10.0
14.6
2
1
3.4
10.0
13.0
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.
197
POWER
COMBUSTION
EXHAUST
FAN MOTOR
FLA
LRA
FLA
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
2.1
4.8
0.57
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
2.1
4.8
0.57
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
2.1
4.8
0.57
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
2.1
4.8
0.57
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage = 452 + 464 + 455
3
1371
=
3
= 457
7
457
= 1.53%
POWER
SUPPLY
MCA
MOCP*
81/81
100/100
85/86
110/110
40
50
43
50
30
40
32
40
87/87
110/110
92/92
110/110
44
50
47
60
34
40
36
40
116/116
150/150
120/120
150/150
57
70
59
70
44
50
46
50
130/130
150/150
135/135
175/175
66
80
68
80
54
70
56
70