Physical Data - Bryant 579F User Manual

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

UNIT 579F
FURNACE SECTION
Rollout Switch Cutout Temp (F)†
Burner Orifice Diameter (in. ...drill size)
Natural Gas
Thermostat Heat Anticipator Setting (amps)
208/230, 575
460 v
Gas Input
Efficiency (Steady State) (%)
Temperature Rise Range
Manifold Pressure (in. wg)
Natural Gas
Gas Valve Quantity
Field Gas Connection Size (in.-FPT)
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
LOW-PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
FREEZE PROTECTION THERMOSTAT (F)
Opens
Closes
OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.)
RETURN-AIR FILTERS
Quantity...Size (in.)
POWER EXHAUST
LEGEND
Bhp
— Brake Horsepower
TXV
— Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of condenser coil and lower portion of evapora-
tor coils; and Circuit 2 uses the upper portion of both coils.
UNIT
579F
*Base unit weight does not include electric heaters, copper coils, economizer,
power exhaust, barometric relief or crating. See Options and Accessories table
below for more information.
OPTION/
ACCESSORY
Barometric Relief Damper
Power Exhaust
EconoMi$er IV
Cu Condenser Coil
Cu Condenser and Evaporator Coils
Roof Curb (14-in. curb)
Horizontal Adapter Curb (Pre-Assembled)
Horizontal Adapter Curb (Field-Assembled)
Hail Guard
LEGEND
Cu — Copper
PHYSICAL DATA — 579F180-300 (cont)
180
190
0.1285...30/0.136...29
Stage 1
0.98
Stage 2
0.44
Stage 1
0.80
Stage 2
0.44
Stage 1
172,000/225,000
Stage 2
230,000/300,000
81
15-45/20-50
3.3
1
3
/
4
OPERATING AND RIGGING WEIGHTS
180
lb
kg
1650
748
1800
OPTIONS AND ACCESSORIES
lb
50
85
90
150
280
200
250
343
60
216
190
0.1285...30/0.136...29
0.98
0.44
0.80
0.44
206,000/270,000
275,000/360,000
81
15-45/20-50
3.3
1
3
/
4
Cleanable
2...20 x 25 x 1
1...20 x 20 x 1
Throwaway**
4...20 x 20 x 2
4...16 x 20 x 2
/
Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
1
2
†Rollout switch is manual reset.
**The 579F300 units requires 2-in. industrial-grade filters capable of handling face
velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equiva-
lent).
NOTE: The 579F units have a low-pressure switch (standard) located on the suc-
tion side.
BASE UNIT OPERATING WEIGHTS*
216
lb
kg
lb
816
1850
NOTE: For 180 and 216 unit sizes add 75 lb (34 kg) for domestic crating. For 240
and 300 unit sizes add 135 lb (61 kg). For export crating add 500 lb (227 kg).
(Weight Adders)
OPTION/ACCESSORY WEIGHTS
180
216
kg
lb
kg
23
50
23
39
85
39
41
90
41
68
150
68
127
280
127
91
200
91
113
250
113
156
343
156
27
60
27
176
240
190
0.1285...30/0.136...29
0.1285...30/0.136...29
0.98
0.44
0.80
0.44
206,000/270,000
275,000/360,000
81
15-45/20-50
3.3
1
3
/
4
426
320
27
44
30 ± 5
45 ± 5
240
kg
lb
839
2000
240
lb
kg
50
23
85
39
90
41
150
68
280
127
200
91
250
113
343
156
60
27
300
190
0.98
0.44
0.80
0.44
206,000/270,000
275,000/360,000
81
15-45/20-50
3.3
1
3
/
4
300
kg
907
300
lb
kg
50
23
85
39
90
41
150
68
280
127
200
91
250
113
343
156
60
27