Bryant 579F User Manual page 188

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

579F240 (20 Tons) (cont)
Temp (F)
Air Entering
Condenser
(Edb)
54/0.65
TC
250
75
SHC
250
kW
15.8
TC
243
85
SHC
243
kW
17.6
TC
236
95
SHC
236
kW
19.5
TC
228
105
SHC
228
kW
21.6
TC
220
115
SHC
220
kW
23.9
TC
218
117
SHC
218
kW
24.3
TC
215
120
SHC
215
kW
25.1
LEGEND
BF
Bypass Factor
Edb
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW
Compressor Motor Power Input
ldb
Leaving Dry-Bulb
lwb
Leaving Wet-Bulb
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
t
=
t
ldb
edb
1.10 x cfm
Wet-bulb temperature corresponding to enthalpy of air
t
=
lwb
leaving evaporator coil (h
total capacity (Btuh)
h
= h
lwb
ewb
4.5 x cfm
Where: h
= Enthalpy of air entering evaporator coil
ewb
PERFORMANCE DATA — 579F (cont)
COOLING CAPACITIES (cont)
58/0.52
62/0.40
250
250
15.8
244
244
17.8
236
236
19.5
228
228
21.6
220
220
23.9
218
218
24.3
215
215
25.1
)
lwb
Evaporator Air Quantity — Cfm
10,000
Evaporator Air — Ewb (F)/BF
67/0.26
256
267
227
200
15.9
16.1
249
262
220
198
17.7
18.0
241
252
212
194
19.7
19.9
234
242
203
190
21.8
22.0
223
232
207
186
23.9
24.2
221
230
205
185
24.4
24.7
218
226
203
183
25.1
25.4
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
BYPASS
FACTOR
(BF)
0.05
1.04
0.10
0.98
0.20
0.87
0.30
0.76
0.40
0.65
0.50
0.55
0.60
0.44
0.70
0.33
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
188
72/0.24
76/0.24
294
314
161
127
16.7
17.1
284
303
158
124
18.5
18.9
274
292
154
121
20.4
20.9
263
281
151
117
22.5
22.9
251
268
147
113
24.7
25.2
249
266
146
112
25.2
25.6
245
145
25.9
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
81
82
83
84
85
Correction Factor
2.07
3.11
4.14
5.18
1.96
2.94
3.92
4.91
1.74
2.62
3.49
4.36
1.53
2.29
3.05
3.82
1.31
1.96
2.62
3.27
1.09
1.64
2.18
2.73
0.87
1.31
1.74
2.18
0.65
0.98
1.31
1.64
80/0.04
under 75
over 85
Use formula
shown below.