Bryant 579F User Manual page 166

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

UNIT
NOMINAL
IFM TYPE
SIZE
V-PH-Hz
208/230-1-60
STD
STD
208/230-3-60
HS
STD
048
460-3-60
(4 tons)
HS
STD
575-3-60
HS
Perfect Humidity
208/230-1-60
STD
STD
208/230-3-60
HS
STD
060
460-3-60
(5 tons)
HS
STD
575-3-60
HS
Perfect Humidity
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
UL
— Underwriters' Laboratories
*The values listed in this table do not include power exhaust. See table at right
for power exhaust requirements.
**Fuse or HACR circuit breaker.
†460v motor
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The UL, Canada units
may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature ± 10%
voltage.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of volt-
age
imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
PERFORMANCE DATA — 581C
581C048-060 UNITS
VOLTAGE
RANGE
COMPRESSOR
Min
Max
QTY
RLA
197
254
1
21
187
254
1
14.1
414
508
1
7.1
518
632
1
6.1
187
254
1
25
187
254
1
17.3
414
508
1
8.4
518
632
1
7.1
452 + 464 + 455
3
1371
=
3
= 457
7
457
COMBUSTION
OFM
FAN MOTOR
LRA
QTY
FLA
FLA
115
1
1.5
0.6
95
1
1.5
0.6
45
1
0.8
0.3
1
0.6
38
0.3†
1
0.8†
150
1
1.5
0.6
123
1
1.5
0.6
70
1
0.8
0.3†
1
0.6
53
0.3†
1
1.9†
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
POWER EXHAUST ELECTRICAL DATA
POWER EXHAUST
PART NO.
CRPWREXH030A01
CRPWREXH021A01
CRPWREXH028A01
CRPWREXH029A01
* — Single or three phase rooftop unit
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power
exhaust MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit.
Determine the new MCA including the power exhaust using the following
formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 581B060—5 unit with MCA = 28.9 and MOCP = 35,
with CRPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would
not change. The MOCP in this example is 35 amps and the MCA New is
below 35; therefore the MOCP is acceptable. If "MCA New" is larger than
the published MOCP, raise the MOCP to the next larger size. For separate
power, the MOCP for the power exhaust will be 15 amps per NEC.
166
CONV
IFM
POWER SUPPLY *
OUTLET
MCA
MOCP**
FLA
NO
32.7
40
4.9
YES
38.7
45
NO
24.0
30
4.9
YES
30.0
35
NO
24.9
30
5.8
YES
30.9
35
NO
11.9
15
2.2
YES
14.6
20
NO
12.3
15
2.6
YES
15.0
20
NO
10.1
15
1.9
YES
12.3
15
NO
10.2
15
2.0
YES
12.4
15
NO
10.3
15
2.6†
YES
12.5
15
NO
39.4
50
6.6
YES
45.4
60
NO
28.9
35
5.8
YES
34.9
40
NO
30.6
35
7.5
YES
36.6
40
NO
13.9
20
2.6
YES
16.6
20
NO
14.7
20
3.4
YES
17.4
20
NO
11.5
15
2.0
YES
13.6
15
NO
12.3
15
2.8
YES
14.4
20
NO
12.2
15
3.4†
YES
14.4
20
Application
MCA
MCA
MCA
usage
(230 v)
(460 v)
(575 v)
036-072
1.6
N/A
036-072
N/A
0.68
ALL*
1.7
N/A
ALL
N/A
0.7
MINIMUM UNIT
DISCONNECT
SIZE
FLA
LRA
31.5
130
37.0
135
23.6
110
29.1
115
24.6
140
30.1
145
11.6
53
14.1
55
12.1
67
14.6
70
9.9
44
11.9
46
10.0
51
12.0
52
10.1
56
12.1
58
38.1
187
43.6
191
28.3
168
33.8
173
30.2
187
35.8
192
13.6
92
16.1
95
14.5
102
17.0
104
11.2
66
13.2
67
12.1
75
14.1
76
12.0
79
14.0
80
MOCP
(for
separate
power
source)
0.64
15
N/A
15
0.68
15
N/A
15